The blueplanet inverters simple connection between low investment costs and high return on investment of large solar power plants with 1500-volt technology.

Economical

For this purpose, the blueplanet inverters has an outstanding power density advantages:

  • fewer inverters for the same power,
  • highly compact design for reduced transport costs,
  • Light weight for easier installation.

Safe and secure

While you carry out commissioning and updates remotely via secure Ethernet communication, the inverter housing withstands harsh conditions such as dust, water jets and salt corrosion near the sea.

Protected in this way, exceptional efficiencies of over 99% ensure consistently high energy yields. The reason for this are innovative power transistors made of silicon carbide - whose thermal superiority also allows for an oversizing of the inverter’s AC power by 1.5 times.

Your benefits at a glance

  • Optimized for solar power plants technology
  • Superior efficiencies and overload capacity through silicon carbide technology
  • Outstanding power density for easy logistics and installation
  • Special properties for extreme environmental conditions
  • Decentralized design or 'Virtual Central' concept possible
  • Overvoltage protection AC/DC and for communication interfaces available
  • Lean commissioning and updates via remote services
Download Datasheet

TECHNICAL DATA

DC input data 87.0 TL3 92.0 TL3 110 TL3 125 TL3 137 TL3 150 TL3
Max. recommended PV generator power 130500 W 138 000 W 165 000 W 187 500 W 205 500 W 225 000 W
MPP range 563 – 1 300 V 591–1 300 V 1) 705 – 1 300 V 875 – 1 300 V 875 – 1 300 V 960 – 1 300 V
Operating range 563 – 1 450 V 591 – 1 450 V 1) 705 – 1 450 V 875 – 1 450 V 875 – 1 450 V 960 – 1 450 V
Rated DC voltage / start voltage 600 V / 645 V 620 V / 675 V 1) 730 V / 805 V 900 V / 1 000 V 900 V / 1 000 V 1 000 V / 1 100 V
Max. no-load voltage 1 500 V 1 500 V 1 500 V 1 500 V 1 500 V 1 500 V
Max. input current 160 A 160 A 160 A 160 A 160 A 160 A
Max. short circuit current Isc max 300 A 300 A 300 A 300 A 300 A 300 A
Number of MPP tracker 1 1 1 1 1 1
Connection per tracker 1-2 1-2 1-2 1-2 1-2 1-2

 

AC output data 87.0 TL3 92.0 TL3 110 TL3 125 TL3 137 TL3 150 TL3
Rated output 87 000 VA 92 000 VA 110 000 VA 125 000 VA 137 000 VA 150 000 VA
Max. power 87 000 VA 92 000 VA 110 000 VA 137 500 VA 137 500 VA 150 000 VA
Line voltage 380 V (3P+PE) 400 V (3P+PE) 480 V (3P+PE) 600 V (3P+PE) 600 V (3P+PE) 660 V (3P+PE)
Voltage range (Ph-Ph) 300 – 580 V 300 – 580 V 300 – 580 V 480 – 760 V 480 – 760 V 480 – 760 V
Rated frequency (range) 50 Hz / 60 Hz (45 – 65 Hz) 50 Hz / 60 Hz (45 – 65 Hz) 50 Hz / 60 Hz (45 – 65 Hz) 50 Hz / 60 Hz (45 – 65 Hz) 50 Hz / 60 Hz (45 – 65 Hz) 50 Hz / 60 Hz (45 – 65 Hz)
Rated current 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A
Max. current 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A 3 x 132.3 A
Reactive power / cos phi 0 – 100 % Snom / 0,30 ind. – 0,30 cap. 0 – 100 % Snom / 0,30 ind. – 0,30 cap. 0 – 100 % Snom / 0,30 ind. – 0,30 cap. 0 – 100 % Snom / 0,30 ind. – 0,30 cap. 0 – 100 % Snom / 0,30 ind. – 0,30 cap. 0 – 100 % Snom / 0,30 ind. – 0,30 cap.
Max. total harmonic distortion (THD) ≤ 3 % ≤ 3 % ≤ 3 % ≤ 3 % ≤ 3 % ≤ 3 %